KNX devices that use KNX Connection Authorization and support Option 1 are, depending on the implementation, vulnerable to being locked and users being unable to reset them to gain access to the device. The BCU key feature on the devices can be used to create a password for the device, but this password can often not be reset without entering the current password. If the device is configured to interface with a network, an attacker with access to that network could interface with the KNX installation, purge all devices without additional security options enabled, and set a BCU key, locking the device.

Even if a device is not connected to a network, an attacker with physical access to the device could also exploit this vulnerability in the same way.

Attack Parameters

Attack Vector
Network
Can be exploited remotely
Attack Complexity
Low
Easy to exploit
Privileges Required
None
No privileges needed
User Interaction
None
No user interaction needed

Impact Assessment

Confidentiality
None
No data leak
Integrity
None
No data modification
Availability
High
Complete denial of service

CVSS Vector v3.1

Weakness Type (CWE)

Vulnerable Products 1

Configuration From (including) Up to (excluding)
Knx Connection_Authorization
cpe:2.3:a:knx:connection_authorization:-:*:*:*:*:*:*:*
— —