Ad

CVE-2026-3611

CRITICAL CVSS 4.0: 10.0 EPSS 0.16%
Updated Mar 13, 2026
Parameter Value
CVSS 10.0 (CRITICAL)
Type CWE-306 (Missing Authentication for Critical Function)
Public PoC No

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module.

Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

Attack Parameters

Attack Vector
Network
Can be exploited remotely
Attack Complexity
Low
Easy to exploit
Attack Requirements
None
No additional conditions
Privileges Required
None
No privileges needed
User Interaction
None
No user interaction needed

Impact Assessment

Confidentiality
High
Complete data leak
Integrity
High
Complete data modification
Availability
High
Complete denial of service

CVSS Vector v4.0