A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted series of network requests can lead to a denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.An attacker can trigger this denial-of-service condition by sending a single Modbus TCP message to port 502 using the Write Single Register function code (6) to write the value 1 to register 4352.
This action changes the Modbus address to 15. After this message is sent, the device will be in a denial-of-service state.
Attack Parameters
Impact Assessment
CVSS Vector v3.1
Weakness Type (CWE)
Vulnerable Products 2
| Configuration | From (including) | Up to (excluding) |
|---|---|---|
|
Socomec Diris_Digiware_M-70_Firmware
cpe:2.3:o:socomec:diris_digiware_m-70_firmware:1.6.9:*:*:*:*:*:*:*
|
— | — |
|
Socomec Diris_Digiware_M-70
cpe:2.3:h:socomec:diris_digiware_m-70:-:*:*:*:*:*:*:*
|
— | — |