CVE-2025-54850

HIGH CVSS 3.1: 7.5 EPSS 0.34%
Updated Sep 26, 2026
Socomec
Parameter Value
CVSS 7.5 (HIGH)
Type CWE-306 (Missing Authentication for Critical Function)
Vendor Socomec
Public PoC No

A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted series of network requests can lead to a denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.An attacker can trigger this denial-of-service condition by sending a sequence of Modbus RTU over TCP messages to port 503 using the Write Single Register function code (6).

The attack sequence begins with a message to register 58112 with a value of 1000, indicating that a configuration change will follow. Next, a message is sent to register 29440 with a value corresponding to the new Modbus address to be configured. Finally, a message to register 57856 with a value of 161 commits the configuration change.

After this configuration change, the device will be in a denial-of-service state.

Attack Parameters

Attack Vector
Network
Can be exploited remotely
Attack Complexity
Low
Easy to exploit
Privileges Required
None
No privileges needed
User Interaction
None
No user interaction needed

Impact Assessment

Confidentiality
None
No data leak
Integrity
None
No data modification
Availability
High
Complete denial of service

CVSS Vector v3.1

Vulnerable Products 2

Configuration From (including) Up to (excluding)
Socomec Diris_M-70_Firmware
cpe:2.3:o:socomec:diris_m-70_firmware:1.6.9:*:*:*:*:*:*:*
— —
Socomec Diris_M-70
cpe:2.3:h:socomec:diris_m-70:-:*:*:*:*:*:*:*
— —